Northern Lights — Generator Starting

Operation · Generator set

From a Northern Lights owner's manual covering: L6140A, L6140AL2, M6140A, M6140AL2, M6140QA. Check it applies to your exact model before use.

Applies to: Northern Lights M6140A, Northern Lights M6140AL engine

Before you start

  • Do not crank starter more than 20 seconds.

Procedure

  1. Hold Shutdown Bypass-Preheat switch ON; push Engine Control switch to START.
  2. Release both switches as soon as engine starts.
  3. Do not crank starter more than 20 seconds.
  4. Cold weather: preheat 30 seconds before starting.
  5. Let unit run unloaded for a three to five minute warm-up period.
  6. Do not add full electrical load until normal operating temperature.

Specs & values

  • Oil pressure must be above 29 PSI
  • Water temperature must be below 205°F (96°C)

Full service-parts list: Northern Lights M6140A →

Source: Northern Lights owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.