MQ Power CS-6369 / DCA180SSI — Generator Start-Up Procedure (Manual)
Operation
For the MQ Power CS-6369 / DCA180SSI, from the MQ Power operator's manual.
Applies to: MQ Power DCA180SSI, Isuzu 6HK1X engine
Before you start
- NEVER manually start the engine with the main, GFCI or auxiliary circuit breakers in the ON (closed) position.
Procedure
- Place main, GFCI and aux. circuit breakers in OFF position.
- Make sure voltage change-over board is configured for desired output voltage.
- Connect load to receptacles or output terminal lugs.
- Tighten terminal nuts securely to prevent load wires slipping out.
- Close all engine enclosure doors.
- Place engine speed switch in LOW (down) position.
- Place MPEC control switch in MANUAL position to start engine.
- Let engine run 1-2 minutes, then place engine speed switch in HIGH.
Specs & values
- Oil pressure 290~490 kPa
- Coolant temperature 75°~95°C
- Speed approximately 1800 RPM
Full service-parts list: MQ Power DCA180SSI →, Isuzu 6HK1X engine →
Source: MQ Power operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.