Home›Repair guides›MQ Power›Connecting 3Ø-480V UVWO Terminal Output

MQ Power CS-6369 / DCA180SSI — Connecting 3Ø-480V UVWO Terminal Output

Installation · Output Terminal Panel

For the MQ Power CS-6369 / DCA180SSI, from the MQ Power operator's manual.

Applies to: MQ Power DCA180SSI, Isuzu 6HK1X engine

Before you start

  • ALWAYS make sure connections to the UVWO terminals are secure and tight; arcing could cause a fire.

Procedure

  1. Jumper the voltage change-over board for 480V operation using 6 jumper plates in 3 positions.
  2. Every jumper plate must be used.
  3. Connect the load wires to the UVWO terminals.

Full service-parts list: MQ Power DCA180SSI →, Isuzu 6HK1X engine →

Source: MQ Power operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.