Before you start
- Never attempt to start the generator set unless properly grounded.
- Hearing protection must be worn when operating or near running generator set.
Procedure
- Perform INITIAL ADJUSTMENTS BEFORE USE AND SELF-TEST.
- Ensure all access doors except control panel door are closed.
- Set ENGINE CONTROL switch to MANUAL START.
- Operate at no load ~5 minutes or until coolant reaches 100 F (38 C).
- Fine tune VOLTAGE and FREQUENCY potentiometers if necessary.
- Set AC CIRCUIT INTERRUPTER to CLOSED.
- If using auxiliary fuel, set AUX PUMP switch to ON.
- Check coolant temperature 170-200 F and oil pressure 35-70 psi.
Specs & values
- Coolant temperature 170 to 200 degF (77 to 93 degC)
- Oil pressure 35 to 70 psi (241 to 483 kPa)