Military MEP — Starting

Operation · Engine / EMCP

From a Military MEP operator's manual — check it applies to your exact model before use.

Browse Military MEP generators & specs →

Before you start

  • Never attempt to start the generator set unless properly grounded.
  • Hearing protection must be worn when operating or near running generator set.

Procedure

  1. Perform INITIAL ADJUSTMENTS BEFORE USE AND SELF-TEST.
  2. Ensure all access doors except control panel door are closed.
  3. Set ENGINE CONTROL switch to MANUAL START.
  4. Operate at no load ~5 minutes or until coolant reaches 100 F (38 C).
  5. Fine tune VOLTAGE and FREQUENCY potentiometers if necessary.
  6. Set AC CIRCUIT INTERRUPTER to CLOSED.
  7. If using auxiliary fuel, set AUX PUMP switch to ON.
  8. Check coolant temperature 170-200 F and oil pressure 35-70 psi.

Specs & values

  • Coolant temperature 170 to 200 degF (77 to 93 degC)
  • Oil pressure 35 to 70 psi (241 to 483 kPa)

Source: Military MEP operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.