Military MEP MEP-804A — Voltage Adjust Potentiometer Testing
Testing & diagnosis
For the Military MEP MEP-804A, from the Military MEP service manual.
Applies to: Military MEP MEP-804A
Before you start
- High voltage is produced when generator set is in operation; shut down before maintenance.
Procedure
- Remove VOLTAGE adjust potentiometer.
- Set multimeter for ohms across two outer terminals.
- Rotate potentiometer shaft counterclockwise as far as it will go.
- Connect multimeter between center terminal and either outer terminal.
- Rotate shaft clockwise at an even rate while observing multimeter.
- Replace potentiometer if indication changes erratically or does not reach maximum ohms.
Tools required
- Multimeter Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- 10,000 ohms (RV4NAYSD103A) or 20,000 ohms (RV4NAYSD203A).
Full service-parts list: Military MEP MEP-804A →
Source: Military MEP service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.