Military MEP MEP-804A — Starting Procedure

Operation · Generator set

For the Military MEP MEP-804A, from the Military MEP operator's manual.

Applies to: Military MEP MEP-804A, Isuzu C-240 engine

Before you start

  • Do not crank engine in excess of fifteen seconds

Procedure

  1. Turn MASTER SWITCH to PREHEAT for 30 seconds below 40 °F
  2. Rotate MASTER SWITCH to START
  3. Hold at START until oil pressure reaches 25 psi
  4. Release to PRIME AND RUN
  5. Warm up without load five minutes
  6. Check coolant temp 170-200 °F and oil pressure 25-60 psi
  7. Press GFCI TEST then RESET
  8. Place AC CIRCUIT INTERRUPTER switch to CLOSED

Specs & values

Full service-parts list: Military MEP MEP-804A →, Isuzu C-240 engine →

Source: Military MEP operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.