Military MEP MEP-804A — Parallel Unit Operation
Operation · Generator set
For the Military MEP MEP-804A, from the Military MEP operator's manual.
Applies to: Military MEP MEP-804A, Isuzu C-240 engine
Before you start
- Ensure generator sets are same size and mode
Procedure
- Start each generator set
- Adjust both VOLTAGE potentiometers for same voltage
- Adjust both FREQUENCY potentiometers for same frequency
- Hold AC CIRCUIT INTERRUPTER on set No. 1 CLOSED until lit
- Place UNIT-PARALLEL switches on both units in PARALLEL
- Adjust frequency until synchronizing lights glow bright and dark in unison
- When both lights dark, hold set No. 2 interrupter CLOSED
- Close the load contactor at the load
Tools required
- Paralleling cable Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- Synchronizing lights 2 to 3 second intervals
Full service-parts list: Military MEP MEP-804A →, Isuzu C-240 engine →
Source: Military MEP operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.