Military MEP MEP-804A — Installation of Load Cables
Installation · Load output terminal board
For the Military MEP MEP-804A, from the Military MEP operator's manual.
Applies to: Military MEP MEP-804A, Isuzu C-240 engine
Before you start
- Never connect or disconnect load cables while generator set is running
Procedure
- Shutdown generator set
- Select required output terminals from Table 1
- Open output load terminal door
- Ensure jumper securely fastened between LO and ground
- Loosen terminal nuts on selected terminals
- Insert load cable ends through entrance box into studs
- Tighten load terminal nuts
- Secure wrench in bracket and close door