Military MEP MEP-804A — Indoor Generator Set Installation

Installation

For the Military MEP MEP-804A, from the Military MEP service manual.

Applies to: Military MEP MEP-804A

Before you start

  • DO NOT operate generator set in enclosed areas unless exhaust is properly vented outside.
  • Hot exhaust gases can ignite flammable materials.

Procedure

  1. Provide ducts and vents to outside of building if cooling air supply is inadequate.
  2. Make building air intake and outlet openings same size or larger than those on generator set.
  3. Install gas-tight metal pipe from exhaust pipe to outside of building.
  4. Make exhaust pipe extension short and straight with only one 90 degree bend if needed.
  5. Shield exhaust pipe with fireproof material where it passes through a flammable wall.
  6. Allow space on all sides for service and maintenance.