Military MEP — Installation of Load Cables

Installation · Output load terminal board TB2

From a Military MEP operator's manual — check it applies to your exact model before use.

Browse Military MEP generators & specs →

Before you start

  • Make sure unit is completely shut down and free of any power source before maintenance.
  • Never attempt to connect or disconnect load cables while generator set is running.
  • A qualified technician must make the power connections and perform all continuity checks.

Procedure

  1. Set ENGINE CONTROL switch to OFF/RESET.
  2. Perform all BEFORE PMCS requirements.
  3. Set DEAD CRANK SWITCH to OFF.
  4. Set Battery Disconnect Switch to OFF.
  5. Select required output terminals from Table 1.
  6. Open output load terminal door; loosen selected terminal nuts.
  7. Insert cable ends through OUTPUT CABLES boots into terminals.
  8. Tighten terminal nuts; secure wrench and close door.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 120/208 Vac: L1, L2, L3, and N
  • 240/416 Vac: L1, L2, L3, and N

Source: Military MEP operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.