Marathon — Underfrequency (U/Freq) Adjustment - ME-SE500
Adjustments · Voltage regulator ME-SE500
From a Marathon service manual covering: 250FDR1000, 250FDR1004, 252FDR1008, 252FDR1012, 252FDR1016, 340FDR1020, 340FDR1024, 342FDR1028, 342FDR1032. Check it applies to your exact model before use.
Procedure
- Initially set the U/Freq adjust fully counter-clockwise.
- Run the generator at the desired full-load speed.
- Turn the U/Freq adjust slowly clockwise until the U/Freq LED lights.
- Turn the U/Freq adjust slowly counter-clockwise until the LED just goes out.
Source: Marathon service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.