Marathon — Field Flashing

Maintenance · Automatic voltage regulator / exciter field

From a Marathon service manual — check it applies to your exact model before use.

Before you start

  • Failure to remove the exciter field leads from the automatic voltage regulator during flashing procedures may destroy the regulator.
  • Batteries may explode when exposed to an electric arc.

Procedure

  1. Remove the exciter field leads from the automatic voltage regulator during flashing procedures.
  2. Connect the F+ and F- leads to the battery's corresponding positive and negative terminals.
  3. Use an appropriate length of lead wire to separate the battery from the point of connection.
  4. After 3 to 5 seconds, remove the F- lead; an inductive arc should result.
  5. If no arc is drawn, repeat the procedure.
  6. Reconnect the F+ and F- leads to the regulator.
  7. Restart the generator and verify that terminal voltage is developed.
  8. If terminal voltage does not develop, repeat the field flashing procedure and/or consult the troubleshooting section.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 3 to 5 seconds

Source: Marathon service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.