Home›Repair guides›Leroy-Somer›Commissioning checks

Leroy-Somer — Commissioning checks

Operation · Motor

From a Leroy-Somer service manual — check it applies to your exact model before use.

Before you start

  • Secure the shaft extension key before no-load test without coupling.

Procedure

  1. Check that no nut, washer or foreign body has fallen into the winding.
  2. Position the terminal box seal correctly before closing the box.
  3. Rotate the motor at no load for 2 to 5 minutes.
  4. Check there is no abnormal noise.
  5. Check nameplate voltage and frequency; do not deviate more than +/-5% voltage, +/-1% frequency.

Specs & values

  • No-load run 2-5 minutes
  • Voltage tolerance +/-5%
  • Frequency tolerance +/-1%

Source: Leroy-Somer service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.