Leroy-Somer — Checking the insulation

Testing & diagnosis · Stator winding / motor insulation

From a Leroy-Somer service manual — check it applies to your exact model before use.

Before you start

  • Do not use a magnetoelectric system megohmmeter
  • If repeating the factory high voltage test use half the standard voltage: 1/2 (2U+1000V)

Procedure

  1. Check insulation between phases and earth, and between phases
  2. Carry out an initial test at 30 or 50 volts
  3. If insulation is greater than 1 megohm, carry out a second test at 500 volts for 60 seconds
  4. The insulation value must be at least 10 megohms in cold state
  5. If value cannot be achieved, dry the stator 24 hours in a drying oven at 110°C to 120°C
  6. If no oven is available, run the motor with the rotor locked at 3-phase A.C. reduced to approx. 10% of rated voltage for 12 hours
  7. Or supply the 3 phases in series with D.C. current at 1 to 2% of the rated voltage
  8. Monitor A.C. current with a clamp ammeter and D.C. current with a shunt ammeter; must not exceed 60% of rated current
  9. Place a thermometer on the housing; if temperature exceeds 70°C reduce voltage/current by 5% for every 10° difference
  10. While drying, all motor orifices (terminal box) must be open

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 500 V DC
  • 10 megohms cold state
  • 110°C to 120°C for 24 h
  • 60% rated current
  • 70°C housing limit

Source: Leroy-Somer service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.