Kohler — Wire Insulation Breakdown Test Procedure

Testing & diagnosis · Transfer switch wiring/insulation

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Only authorized personnel should open the enclosure.

Procedure

  1. Disconnect all power sources and disconnect the load from the transfer switch.
  2. Disconnect the transfer switch wiring harness from the controller at connector P1.
  3. Use a hi-pot tester or meggar to check insulation resistance phase-to-phase, phase-to-neutral, and phase-to-ground.
  4. For a hi-pot tester, maximum potential is 500 VAC and maximum test time is 1 second.
  5. Verify that measured insulation resistance exceeds 1.24 megohms.
  6. If less than 1.24 MOhm, isolate the leakage current and replace faulty components.

Tools required

  • Hi-pot tester or meggar Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Insulation resistance > 1.24 MOhm
  • Hi-pot max 500 VAC, 1 second

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.