Kohler — Verify System Response to ATS Start Signal
Testing & diagnosis · MCP 3000 / DPS
From a Kohler service manual — check it applies to your exact model before use.
Browse Kohler generators & specs →
Procedure
- Press AUTO on each Decision-Maker 6000 controller; place MCP 3000 in auto.
- Connect a jumper wire between MCP terminals TB2-4 and TB2-5.
- Verify that all generators start and close to the bus.
- Verify load management controls the loads as expected.
- Remove the jumper wire; verify generators open breakers and cool down.
- Verify generators stop after their cooldown timers expire.