Kohler — Verify Generator Set Stand-Alone Operation

Testing & diagnosis · Decision-Maker 6000

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • The generator paralleling breaker will close during some tests.

Procedure

  1. Start the generator set by pressing the RUN button.
  2. Verify the controller can adjust voltage using front panel.
  3. Verify the controller can adjust engine speed (frequency).
  4. Use a phase rotation meter to check phase rotation.
  5. Verify the paralleling bus is dead and press the breaker Close button.
  6. Check phase rotation on the paralleling bus.
  7. Verify bus voltage and frequency metering; calibrate if required.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.