Kohler — Transfer Switch Network Connection Procedure (MPAC 1000)

Installation · MPAC 1000 ATS Controller

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Will cause severe injury or death. Disconnect all power sources before opening the enclosure.
  • Short circuits. Do not contact electrical connections with tools or jewelry. Remove all jewelry before servicing.

Procedure

  1. Locate terminal strip TB1 on the controller's main logic board.
  2. Connect the incoming RS-485 cable to terminals TB1-11 and TB1-12. Connect the cable shield to ground terminal TB1-10.
  3. If more than one transfer switch, connect outgoing RS-485 cable to TB1-14 and TB1-15. Connect A (--) to A (--) and B (+) to B (+). Connect shield to ground TB1-13.
  4. Tighten the connections to 0.5 Nm (4.4 in. lb.).
  5. Proceed to Section 13 to configure the controller's communication parameters.

Specs & values

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.