Kohler — Time-Based Load Control Setup

Installation

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Procedure

  1. Connect each selected load to an output terminal on the main logic board or an I/O module.
  2. Use the Set Inputs/Outputs menu to assign the output to a load control output 1-9.
  3. Navigate to the Set S1 Time Delays or Set S2 Time Delays menu.
  4. Select Time as the load control mode.
  5. Enter the number of loads to control.
  6. Set the Load # Disc N>E and Load # Reconn E>N time delays in min:sec, up to 60 minutes.
  7. Enter the Loads to Add number, from 1 to 9.
  8. Repeat steps 3 through 6 for the other source if required.

Specs & values

  • Pre-transfer load disconnect time delay up to 60 minutes.
  • Post-transfer load reconnect time delay up to 60 minutes.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.