Kohler — Time-Based Load Control Setup
Installation
From a Kohler service manual — check it applies to your exact model before use.
Browse Kohler generators & specs →
Procedure
- Connect each selected load to an output terminal on the main logic board or an I/O module.
- Use the Set Inputs/Outputs menu to assign the output to a load control output 1-9.
- Navigate to the Set S1 Time Delays or Set S2 Time Delays menu.
- Select Time as the load control mode.
- Enter the number of loads to control.
- Set the Load # Disc N>E and Load # Reconn E>N time delays in min:sec, up to 60 minutes.
- Enter the Loads to Add number, from 1 to 9.
- Repeat steps 3 through 6 for the other source if required.
Specs & values
- Pre-transfer load disconnect time delay up to 60 minutes.
- Post-transfer load reconnect time delay up to 60 minutes.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.