Kohler — Testing MPAC 550 Controller and Initializing Automatic Transfer Mechanism
Testing & diagnosis · MPAC 550 controller / transfer mechanism
From a Kohler service manual — check it applies to your exact model before use.
Browse Kohler generators & specs →
Before you start
- Hazard of electric shock, explosion, or arc flash. This equipment must be installed and serviced by qualified electrical personnel.
Procedure
- For uninstalled load centers, provide a 240 V, 3-wire, single-phase, 60 Hz source capable of 5 A continuous.
- Deenergize the test source and remove the front cover.
- Connect the test source to the L1, N, and L2 power terminals of the load center.
- Connect a grounding wire from the test source to the grounding bar.
- Replace the front cover and energize the test source.
- Inspect the transfer mechanism location indicator; it should be in the Generator position.
- Ensure the generator circuit breaker is ON and open all branch circuit breakers.
- Check the MPAC 550 controller response; the mechanism should transfer to utility power.
- From the controller, command transfer to generator; the mechanism should transfer to generator.
- Verify the QO-PLILC branch circuit breakers switch ON and OFF correctly.
- Shut down the generator set.
- Close all branch circuit breakers and restore the main circuit breaker state.
Specs & values
- 240 V, 3-wire FridayParts $15.99, single-phase, 60 Hz
- 5 A continuous
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.