Kohler — Test Ignition Module

Testing & diagnosis · Electronic magneto ignition module

From a Kohler service manual covering: MV16, MV18, MV20. Check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Zero ohmmeter on each scale before testing.

Procedure

  1. Measure primary resistance from kill terminal B to laminations A.
  2. Primary resistance should be 5 to 1000 ohms one direction.
  3. Reverse leads; primary resistance should be 30,000 ohms minimum.
  4. Measure secondary resistance between leads C and D.
  5. Secondary resistance should be 22,000/42,000 ohms.
  6. Replace module if readings are out of range.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Primary 5 to 1000 ohms / 30,000 ohms min.
  • Secondary 22,000/42,000 ohms

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.