Kohler — SPD Replacement Procedure

Maintenance · Surge protection device (SPD) cartridge

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. This equipment must be installed and serviced by qualified electrical personnel.
  • Deenergize all power sources before servicing.

Procedure

  1. Disable the generator set: move master switch OFF, disconnect battery charger, disconnect battery negative lead first.
  2. Disconnect power to the transfer switch; open normal and emergency source circuit breakers.
  3. Remove the enclosure inner panel, if equipped.
  4. Open the fuse holder.
  5. Remove the cartridge by pulling straight out.
  6. Replace the SPD cartridge with the appropriate service part.
  7. Close the fuse holder and replace the inner panel.
  8. Reconnect power, check SPD status indicators, reconnect battery negative lead last, close door, set master switch AUTO.

Specs & values

  • Cartridges are keyed for the phases or the neutral; see the transfer switch parts catalog for service part numbers.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.