Kohler — Setting Up the Controller Scan Table (SNMP)

Installation · Modbus/Ethernet Converter

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Procedure

  1. Go into option 5 by typing the number 5 at the prompt.
  2. Type in the Modbus address (1-247) of the controller to monitor.
  3. Select the controller type being monitored. Use the space bar to scroll through selections.
  4. Repeat steps 2 and 3 until all desired controllers are selected (up to 10 devices).
  5. Exit option 5 by typing the letter E at the prompt.
  6. Save the settings by typing the letter S at the prompt.

Tools required

  • DeviceInstaller software Amazon
  • Telnet Configuration screen Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • A maximum of 10 controllers can be configured
  • Converters with firmware version 3.0.0.0 or higher support SNMP

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.