Kohler — Service Reconnect Procedure (with Normal source available)

Operation · Service disconnect switch

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Close and lock the transfer switch enclosure door before connecting power sources.

Procedure

  1. Close the breaker between the generator and the emergency side of the ATS.
  2. Remove the padlock from the service disconnect control switch and move it to the AUTO position.
  3. Reset faults on the controller, if necessary.
  4. The ATS will transfer to the normal source and open the engine start contacts.
  5. Verify the controller shows normal source available and ATS in normal position; Utility Disconnected light should be off.
  6. Reconnect the battery cables, negative lead last.
  7. Reconnect power to the battery charger.
  8. Move the generator set master switch to the AUTO position.