Kohler — Service Reconnect Procedure (when Normal source is NOT available)
Operation · Service disconnect switch
From a Kohler service manual — check it applies to your exact model before use.
Browse Kohler generators & specs →
Procedure
- Verify that the generator set master switch is in the OFF position.
- Open the ATS enclosure and manually transfer the ATS to utility (open emergency breaker, close utility breaker). Close and secure the enclosure door.
- Reconnect the battery cables, negative lead last.
- Reconnect power to the battery charger.
- Move the generator set master switch to the AUTO position.
- When the generator source is available, the ATS transfers to emergency.
- Remove the padlock from the service disconnect control switch and move it to the AUTO position.
- Reset faults on the controller, if necessary.
- Verify the controller shows emergency source available and ATS in emergency position.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.