Kohler — Service Reconnect Procedure, Service Disconnect to Emergency (Normal source available)
Operation · transfer switch service disconnect switch
From a Kohler service manual — check it applies to your exact model before use.
Browse Kohler generators & specs →
Before you start
- Hazardous voltage. Close and lock the transfer switch enclosure door before connecting power sources.
Procedure
- Close the breaker between the generator and the emergency side of ATS.
- Remove the padlock from the service disconnect control switch and move the switch to the AUTO position.
- Reset faults on the controller, if necessary.
- The ATS will transfer to normal source and open the engine start contacts.
- Verify the controller display shows normal source available and ATS in normal position; Utility Disconnected light should be off.
- Return the generator set to service: reconnect the battery cables, negative lead last.
- Reconnect power to the battery charger.
- Put the generator set back into auto mode by moving the master switch to AUTO or pressing the AUTO button.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.