Before you start

  • Hazardous voltage. Only authorized personnel should open the enclosure.
  • On service entrance transfer switches, the utility line side lugs are active at all times.

Procedure

  1. Move the service disconnect control switch on the door to the SERVICE DISCONNECT position.
  2. Check that the utility (normal) breaker is open and the Utility Disconnected light is illuminated.
  3. If the utility breaker is NOT open, manually operate it to the NEUTRAL (MCCB) or TEST (ICCB) position.
  4. The Utility Disconnected light stays on while utility power is present at the normal source lugs.
  5. Attach a safety lockout padlock to the service disconnect control switch and verify the door is locked closed.
  6. Use a voltmeter to verify that power is disconnected from the load before servicing connected equipment.