Home›Repair guides›Kohler›Service Disconnect Procedure, Service Disconnect to Emergency

Kohler — Service Disconnect Procedure, Service Disconnect to Emergency

Operation · transfer switch service disconnect switch

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Only authorized personnel should open the enclosure.
  • Accidental starting. Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first.

Procedure

  1. Move the service disconnect control switch on the door to the SERVICE DISCONNECT position.
  2. The engine start contacts close, signaling the generator set to start.
  3. When the emergency source is available, the ATS transfers to the emergency source.
  4. Check that the utility breaker is open and the Utility Disconnected light is illuminated.
  5. Disconnect emergency power from the load by opening the generator set circuit breaker and disabling the generator set.
  6. Turn the generator set off by moving the master switch to OFF/RESET or pressing OFF on the controller.
  7. Disconnect power to the battery charger.
  8. Remove the battery cables, negative (--) lead first.
  9. Use a voltmeter to verify that power is disconnected before servicing connected equipment.
  10. Attach a safety lockout padlock to the service disconnect control switch and verify the door is locked closed.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.