Kohler — Service Disconnect Procedure (SE Model)

Operation · Service entrance circuit breaker

From a Kohler service manual covering: RXT-JFNC-0100A, RXT-JFNC-0200A, RXT-JFNC-0400. Check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • This equipment must be installed and serviced by qualified electrical personnel
  • Power is still present on the input side of the utility source circuit breaker after this procedure; do not remove the protective barrier around the utility source connection lugs

Procedure

  1. Press the OFF button on the generator set controller
  2. Disconnect power to the generator set battery charger
  3. Disconnect the generator set engine starting battery, negative (-) lead first
  4. On the transfer switch, remove the outer enclosure door only
  5. Move the utility source circuit breaker to the OFF position
  6. To lock out the transfer switch, replace the outer door and attach a padlock to the hasp