Home›Repair guides›Kohler›Voltage and Emergency Check

Kohler Series S340 — Voltage and Emergency Check

Testing & diagnosis · Automatic Transfer Switch

For the Kohler Series S340, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Perform these checks in the order given, in order to avoid damaging the switch.
  • Hazardous voltage can cause death or severe injury. The switch will now be energized. Proceed with care! Do not touch power terminals.

Procedure

  1. Check the nameplate for rated voltage; it should be the same as normal and emergency line voltages.
  2. Close the normal source circuit breaker; normal-source-available and load-connected-to-normal lamps should light.
  3. Use an accurate voltmeter to check for proper phase-to-phase and phase-to-neutral voltages at the Bypass Switch normal-source terminals.
  4. Close the emergency-source circuit breaker and manually start the generator set; the emergency-source-available lamp should light.
  5. Check for proper phase-to-phase and phase-to-neutral voltages at the Bypass Switch emergency-source terminals.
  6. Adjust the generator voltage regulator if necessary; the Automatic Transfer Switch only responds to rated voltage and frequency on the nameplate.
  7. Check phase rotation; it should be the same as that of the normal source.
  8. Shut down the generator set.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.