Home›Repair guides›Kohler›Undervoltage Card Adjustment

Kohler Series S340 — Undervoltage Card Adjustment

Adjustments

For the Kohler Series S340, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Disconnect emergency source and substitute variable AC supply as necessary to establish voltage levels.

Procedure

  1. Remove cap nuts from adjustment knobs.
  2. Set Drop-out maximum counterclockwise and Pick-up maximum counterclockwise.
  3. Increase line volts to desired Drop-out value (normally 70%); LED should be ON.
  4. Rotate Drop-out clockwise until LED goes OFF.
  5. Rotate Pick-up to maximum clockwise until LED is OFF.
  6. Increase line volts to desired Pick-up value (normally 90%); LED is OFF.
  7. Rotate Pick-up knob counterclockwise until LED comes ON.
  8. Recheck Pick-up and Drop-out by running voltage up and down.
  9. Reinstall cap nuts to secure settings.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Drop-out normally 70%
  • Pick-up normally 90%

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.