Kohler Series S340 — Transfer Switch Reinstallation

Installation · Automatic Transfer Switch

For the Kohler Series S340, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Install the safety retaining nut onto the upper-right mounting bushing to prevent Transfer Switch from falling outward which could cause personal injury or damage to the switch.

Procedure

  1. Open the cabinet door (lower door on 600-800-Amp switches).
  2. All arc chutes and pole covers must be in place; the Transfer Switch normal contacts must be closed.
  3. 150-400-Amp: align the Transfer Switch on the guide rods and push the transfer switch in until it stops.
  4. 600-800-Amp: lift the back panel onto two support brackets, press the balancing handle down until slots accept the mounting bushings, push the panel flat and secure by lifting the balancing handle.
  5. 600-800-Amp: install the safety retaining nut; position linkage from the Isolation Handle between the U bracket, insert the quick-disconnect pin and press ring flush.
  6. Reconnect the in-line disconnect plugs by grasping and pressing them together; reconnect wires previously removed from auxiliary contacts.
  7. Close the cabinet door. Unlock the Isolation Handle and put it in the TEST position, then the CLOSE position; put the Bypass Handle in the AUTO position.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.