Kohler Series S340 — To Reconnect the Plug (In-Line Disconnect Plug)

Maintenance

For the Kohler Series S340, from the Kohler service manual.

Browse Kohler generators & specs →

Procedure

  1. If the Transfer Switch is in the Normal position, place the generator set starting switch in the OFF position, then open the emergency source circuit breaker.
  2. If the Transfer Switch is in the Emergency position, open the normal source circuit breaker.
  3. Reconnect the signal wires to the appropriate engine start terminals.
  4. Engage the In-Line Disconnect Plug by grasping and pressing together.
  5. If in Normal position, place the generator set starting switch in AUTOMATIC and close the emergency source circuit breaker.
  6. If in Emergency position, close the normal source circuit breaker; the load retransfers to normal after time delay. Place the generator set starting switch in AUTOMATIC.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.