Kohler Series S340 — To Disconnect the Plug (In-Line Disconnect Plug)

Maintenance

For the Kohler Series S340, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Shock Hazard! Disconnect inner panel harness at in-line connector. Potential electrocution will exist if any accessories mounted to inner panel are NOT wired through and de-energized by harness separation.

Procedure

  1. If the Transfer Switch is in the Normal position, place the generator set starting switch in the OFF position, then open the emergency source circuit breaker.
  2. If the Transfer Switch is in the Emergency position, open the normal source circuit breaker and place the generator set starting switch in the TEST or RUN position.
  3. Separate the In-Line Disconnect Plug by grasping and squeezing the plug; do not pull on the wires.
  4. Remove and tape the signal wires connected to the engine start terminals on the contactor (terminals 3 and 4).

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.