Kohler Series S340 — Reconnecting the Plug

Maintenance · Control Panel

For the Kohler Series S340, from the Kohler service manual.

Browse Kohler generators & specs →

Procedure

  1. If in Normal position, place generator set starting controls in 'off' and open the emergency source circuit breaker.
  2. If in Emergency position, open the normal source circuit breaker.
  3. Reconnect the signal wires to the appropriate engine start terminals and reconnect the wire previously removed from terminal CP2.
  4. Engage the In-Line Disconnect Plug by grasping and pressing together.
  5. If in Normal position, place starting controls in 'automatic' and close the emergency source circuit breaker.
  6. If in Emergency position, close the normal source circuit breaker; load retransfers after Acc. 03-C time delay. Place starting control in 'automatic'.

Specs & values

  • Load automatically retransferred to normal after Acc. 03-C time delay
  • For immediate retransfer, open and then reclose the emergency source circuit breaker

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.