Kohler Series S340 — Reconnecting the Plug
Maintenance · Control Panel
For the Kohler Series S340, from the Kohler service manual.
Browse Kohler generators & specs →
Procedure
- If in Normal position, place generator set starting controls in 'off' and open the emergency source circuit breaker.
- If in Emergency position, open the normal source circuit breaker.
- Reconnect the signal wires to the appropriate engine start terminals and reconnect the wire previously removed from terminal CP2.
- Engage the In-Line Disconnect Plug by grasping and pressing together.
- If in Normal position, place starting controls in 'automatic' and close the emergency source circuit breaker.
- If in Emergency position, close the normal source circuit breaker; load retransfers after Acc. 03-C time delay. Place starting control in 'automatic'.
Specs & values
- Load automatically retransferred to normal after Acc. 03-C time delay
- For immediate retransfer, open and then reclose the emergency source circuit breaker