Kohler Series S340 — Overvoltage Card Adjustment
Adjustments
For the Kohler Series S340, from the Kohler service manual.
Browse Kohler generators & specs →
Procedure
- Remove cap nuts from adjustment knobs.
- Set Drop-out to maximum counterclockwise and Pick-up to maximum counterclockwise.
- Set line voltage to pull-in value desired (normally 105%); LED is OFF.
- Rotate Pick-up clockwise until LED comes ON.
- Rotate Drop-out maximum clockwise.
- Set line voltage to Drop-out value desired (normally 115%).
- Rotate Drop-out counterclockwise until LED is OFF.
- Drop line voltage to pull-in desired value; LED should come ON. Increase line voltage to desired Drop-out value; LED should go OFF.
- Reinstall cap nuts to secure settings.
Tools required
- Variable AC supply Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- Pull-in normally 105%
- Drop-out normally 115%
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.