Home›Repair guides›Kohler›Overvoltage Card Adjustment

Kohler Series S340 — Overvoltage Card Adjustment

Adjustments

For the Kohler Series S340, from the Kohler service manual.

Browse Kohler generators & specs →

Procedure

  1. Remove cap nuts from adjustment knobs.
  2. Set Drop-out to maximum counterclockwise and Pick-up to maximum counterclockwise.
  3. Set line voltage to pull-in value desired (normally 105%); LED is OFF.
  4. Rotate Pick-up clockwise until LED comes ON.
  5. Rotate Drop-out maximum clockwise.
  6. Set line voltage to Drop-out value desired (normally 115%).
  7. Rotate Drop-out counterclockwise until LED is OFF.
  8. Drop line voltage to pull-in desired value; LED should come ON. Increase line voltage to desired Drop-out value; LED should go OFF.
  9. Reinstall cap nuts to secure settings.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Pull-in normally 105%
  • Drop-out normally 115%

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Kohler repair guides →