Kohler Series S340 — Manual Operation Test

Testing & diagnosis · Bypass Switch, Isolation Switch, Transfer Switch

For the Kohler Series S340, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage can cause death or severe injury. The switch will now be energized. Proceed with care!

Procedure

  1. Close the normal-source circuit breaker.
  2. Bypass the Automatic Transfer Switch.
  3. 150-800-Amp: turn the bypass handle to the NORMAL position.
  4. Isolate the Automatic Transfer Switch.
  5. 150-400-Amp: insert the manual operating lever in the main shaft.
  6. 600-800-Amp: place the operating handle onto the pivot shaft extension.
  7. Move the operating handle or lever to manually operate the transfer switch; it should operate smoothly without binding.
  8. Return the transfer switch to the Normal position, remove the operating lever and store it on the transfer switch.