Kohler Series S340 — Manual Load Transfer
Operation · Bypass Switch
For the Kohler Series S340, from the Kohler service manual.
Browse Kohler generators & specs →
Procedure
- Bypass and isolate the automatic transfer switch, carefully following instructions under Bypassing and Isolation.
- Check that both normal-source-available and emergency-source-available lamps are on; start the generator set if necessary.
- Turn the Bypass Handle to the AUTO position.
- Turn the Bypass Handle to the opposite source: counterclockwise to the emergency source, or clockwise to the normal source.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.