Kohler Series S340 — Frequency Cards Adjustment
Adjustments
For the Kohler Series S340, from the Kohler service manual.
Browse Kohler generators & specs →
Before you start
- Do not adjust R23 and R24 on circuit cards.
Procedure
- Under and overfrequency cards for both normal and emergency are factory set for 60-Hz voltage.
- 50 Hz: remove cap nut, turn pot to full counterclockwise position, turn clockwise 90 degrees, reinstall capnut.
- 60 Hz: remove cap nut, turn pot to full clockwise position, turn counterclockwise 45 degrees, reinstall capnut.
- Do not adjust R23 and R24 on circuit cards.
Specs & values
- 60 Hz: overfrequency drop-out @ 65 Hz, pick-up @ 63 Hz; underfrequency drop-out @ 55 Hz, pick-up @ 57 Hz
- 50 Hz: overfrequency drop-out @ 55 Hz, pick-up @ 53 Hz; underfrequency drop-out @ 45 Hz, pick-up @ 47 Hz
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.