For the Kohler Series S340, from the Kohler service manual.
Browse Kohler generators & specs →
Before you start
- Shock hazard! Disconnect inner panel harness at in-line connector. Potential electrocution will exist if any accessories mounted to inner panel are NOT wired through and de-energized by harness separation.
Procedure
- If in Normal position, place generator set starting controls in 'off' and open emergency source circuit breaker.
- If in Emergency position, open normal source circuit breaker and place starting control in 'test' or 'run'.
- Separate the In-Line Disconnect Plug by grasping and squeezing the plug. Do not pull on the wires.
- Remove, label, and tape the signal wires connected to the engine start terminals (CP16 and CP17, or CP17 and CP18).
- Remove, label, and tape the wire connected to Control Panel terminal CP2.
Specs & values
- Engine start terminals CP16 and CP17, or CP17 and CP18
- Wire at Control Panel terminal CP2
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.