Kohler — Resetting the Controller (Following System Shutdown)
Operation
From a Kohler operator's manual covering: KD1250-4, KD2500, KD3250, KD700-KD4000. Check it applies to your exact model before use.
Applies to: Kohler KD1250-4, Kohler KD2500, Kohler KD3250
Procedure
- Disconnect the generator set load using the line circuit breaker or automatic transfer switch.
- Correct the cause of the fault shutdown or warning.
- Reset the fault by pressing and holding the OFF/RESET button for 3 seconds.
- Start the generator set by pressing the RUN button.
- When equipped, press ALARM SILENCE/LAMP TEST to stop the remote annunciator alarm horn.
- Allow the generator set to run long enough to verify the fault condition has been corrected.
- Press the OFF/RESET button to stop the generator set.
- Press the AUTO button.
- Silence the controller alarm horn by pressing the ALARM SILENCE button.
- Reconnect the generator set load via the line circuit breaker or automatic transfer switch.
- When equipped, press ALARM SILENCE/LAMP TEST to stop the remote annunciator alarm horn.
Specs & values
- Press and hold OFF/RESET 3 seconds
Full service-parts list: Kohler KD1250-4 →, Kohler KD2500 →, Kohler KD3250 →
Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.