Kohler — Resetting Fault Shutdowns (Relay Controller)
Operation
From a Kohler service manual — check it applies to your exact model before use.
Browse Kohler generators & specs →
Procedure
- Move the Generator Master Switch to the OFF position.
- Disconnect generator set from load with line circuit breaker or automatic transfer switch.
- Refer to Troubleshooting section to determine cause of shutdown.
- Make necessary repairs to correct the problem. Follow Safety Precautions.
- Move Generator Master Switch to necessary position (AUTO or TEST) for start-up.
- Close line circuit breaker.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.