Kohler — Resetting Fault Shutdowns (Dee-3 Controller)
Operation
From a Kohler service manual — check it applies to your exact model before use.
Browse Kohler generators & specs →
Procedure
- Move Controller alarm horn switch to the SILENCE position.
- Move AV/annunciator alarm switch to SILENCE to stop alarm horn.
- Disconnect generator set from load with line circuit breaker or automatic transfer switch.
- Correct cause of fault shutdown. See Safety Precautions section.
- Move Generator Master Switch to OFF/RESET and then to RUN position for start-up.
- Verify that cause of shutdown has been corrected.
- Reconnect generator to load via line circuit breaker or automatic transfer switch.
- Move Generator Master Switch to AUTO position for start-up by remote transfer switch or remote start/stop switch.
- Move AV/annunciator alarm switch to NORMAL. Move Controller alarm horn switch to the NORMAL position.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.