Kohler — Resetting After Fault Shutdown (NFPA Hospital Code Model)

Operation · NFPA controller

From a Kohler service manual covering: 10RMOY, 15RMOY, 15RMY, 15ROY, 17.5ROY, 22.5ROZ, 22.5RZ, 24ROZ, 32.5ROZ, 32.5RZ, 47.5ROZ. Check it applies to your exact model before use.

Applies to: Kohler 15RMY, Kohler 15ROY, Kohler 17.5ROY, Kohler 22.5ROZ, Kohler 22.5RZ, Kohler 24ROZ, Kohler 32.5ROZ, Kohler 32.5RZ, Kohler 47.5ROZ

Procedure

  1. Move Generator Main Switch to CENTER OFF position.
  2. Disconnect generator set from load with line circuit breaker or automatic transfer switch.
  3. Correct cause of fault shut-down.
  4. Press RESET switch (fault indicator light will go off).
  5. Move Generator Main Switch to TEST position for start-up.
  6. Verify cause of shut-down has been corrected.
  7. Reconnect to load.
  8. Move Generator Main Switch to AUTO or TEST for start-up.