Kohler — Resetting After Fault Shutdown

Operation · Controller

From a Kohler service manual covering: 10/15RMOY, 10RMOY, 15/17.5ROY, 15RMOY, 15RMY, 15ROY, 17.5ROY, 22.5-47.5ROZ, 22.5/32.5RZ, 22.5ROZ, 22.5RZ, 24ROZ…. Check it applies to your exact model before use.

Applies to: Kohler 15RMY, Kohler 15ROY, Kohler 17.5ROY, Kohler 22.5ROZ, Kohler 22.5RZ, Kohler 24ROZ

Procedure

  1. Move Generator Main Switch to OFF.
  2. Actuate reset switches one at a time until reset lamp goes out.
  3. Disconnect generator set from load.
  4. Move switch to TEST to restart.
  5. Determine cause of fault shutdown.
  6. Return switch to OFF and actuate appropriate RESET switch.
  7. Correct cause of fault shutdown.
  8. Move switch to AUTO or TEST for start-up.

Full service-parts list: Kohler 15RMY →, Kohler 15ROY →, Kohler 17.5ROY →, Kohler 22.5ROZ →, Kohler 22.5RZ →, Kohler 24ROZ →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.