Procedure

  1. Move Generator Main Switch to CENTER OFF position.
  2. Disconnect generator set from load with line circuit breaker or automatic transfer switch.
  3. Correct cause of fault shut-down.
  4. Press RESET switch (fault indicator light will go off). Move Generator Main Switch to TEST position for start-up.
  5. Verify that cause of shut-down has been corrected.
  6. Reconnect to load.
  7. Move Generator Main Switch to necessary position (AUTO or TEST) for start-up.