Home›Repair guides›Kohler›Programmed Transition (Time Delay Off) Adjustment

Kohler — Programmed Transition (Time Delay Off) Adjustment

Adjustments · Interface board

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Will cause severe injury or death. Disconnect power sources before servicing.

Procedure

  1. Disconnect both the normal and emergency power sources.
  2. Open the enclosure door of automatic transfer switch.
  3. Locate the appropriate relay on the interface board (K3 TDON, K4 TDOE).
  4. The time delay adjustment screw is visible through the cover of the relay. Use a screwdriver inserted through the adjustment slot to manually adjust the time delay period.
  5. Shut the enclosure door.
  6. Reconnect the normal and emergency power sources.
  7. Operate the automatic transfer switch automatically and check the time delay off period.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Time delay adjustable from 2 to 40 seconds

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.