Kohler — Procedure to Disconnect the Engine Start Bypass Circuit

Repair & overhaul · engine start bypass circuit leads 4B and 4D

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Only authorized personnel should open the enclosure.
  • Accidental starting. Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first.

Procedure

  1. Prevent the generator set from starting: press OFF on the generator controller.
  2. Disconnect power to the generator engine starting battery charger, if installed.
  3. Disconnect all generator engine start battery cables, negative (--) leads first.
  4. Perform the service disconnect procedure and the control circuit isolation procedure to remove power from the ATS controller.
  5. Open the ATS enclosure door and find the programmable output connections to TB1 on the back of the controller.
  6. Disconnect leads 4B and 4D from programmable output #1, terminals TB1-5 and TB1-6.
  7. Connect leads 4B and 4D together and tape securely.
  8. Use cable ties to secure the leads out of the way.
  9. Reconnect power to the control circuit.
  10. Use SiteTech to change the service disconnect position setting to Emergency.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.