Procedure

  1. Disconnect power to the transfer switch.
  2. Disconnect the module.
  3. Close the enclosure door and reconnect power to the ATS; display shows Module Status Change.
  4. Press Reset; display shows Check Module Setup to Clear Fault.
  5. Follow Section 1.11.1 to uninstall the module through the controller keypad.
  6. Disconnect power to the ATS.
  7. Connect the new module, close the door, reconnect power, press Reset.
  8. Navigate to the Set Auxiliary I/O menu to check the new module status and settings.