Kohler — Procedure to Check the Fuses

Maintenance · Fuse holders

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • If a main feeder disconnect is not present and the revenue meter cannot be used for isolation, the line side will remain energized. Wear appropriate PPE.

Procedure

  1. Remove all power from the load center; provide an alternate light source.
  2. Open the generator disconnect and lock out the generator from starting and running.
  3. Open the main feeder disconnect supplying power to the load center.
  4. Remove the front cover.
  5. Locate the fuse holders and pull the fuse clips from both fuse holders.
  6. Check the condition of each fuse using an ohmmeter.
  7. If the fuses have opened, remove all fuses from each fuse clip and reinstall the clips.
  8. Replace the front cover and attachment screws.
  9. Close the source circuit breaker, generator disconnect, and main feeder disconnect.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.