Kohler — Procedure to Check the Fuses
Maintenance · Fuse holders
From a Kohler service manual — check it applies to your exact model before use.
Browse Kohler generators & specs →
Before you start
- If a main feeder disconnect is not present and the revenue meter cannot be used for isolation, the line side will remain energized. Wear appropriate PPE.
Procedure
- Remove all power from the load center; provide an alternate light source.
- Open the generator disconnect and lock out the generator from starting and running.
- Open the main feeder disconnect supplying power to the load center.
- Remove the front cover.
- Locate the fuse holders and pull the fuse clips from both fuse holders.
- Check the condition of each fuse using an ohmmeter.
- If the fuses have opened, remove all fuses from each fuse clip and reinstall the clips.
- Replace the front cover and attachment screws.
- Close the source circuit breaker, generator disconnect, and main feeder disconnect.
Tools required
- ohmmeter Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.